The J-Y(St)Y cable is used to transmit diagnostics and alarm signals, and is also used in the power supply circuits of alarm systems. It is intended for operation with a rated alternating voltage up to 300V with a frequency of 50 Hz.
It is installed inside buildings in cable channels, along the inner walls. Cables with an alumopolymer screen are used in places exposed to increased electrical noise.
Cable make-up |
Weight of 1 km of cable, kg |
Outer diameter, mm |
Factory length, m |
J-Y(St)Y 2х2х0,8+0,6 FIRE ALARM CABLE | 47,5 |
6,4 |
300 |
Parameters |
Current frequency, kHz |
Normal value |
Resistance of the current-carrying conductor of cable, adjusted to 1 km length and temperature 20 °С, max., Ohm/km, for conductors with diameter, mm: 0,5 0,8 |
DC |
96 36,6 |
Resistance of the current-carrying conductor of cable, adjusted to 1 km length and temperature 20 °С, max., Ohm/km, for conductors with cross-section, mm2: 0,75 |
DC | 26,0 |
Resistance of cable conductor insulation, adjusted for 1 km length and temperature of 20 °С, MOhm*km (min.) | DC | 150 |
Rated alternating voltage, V: | 0,05 | 300 |
Test voltage for 1 minute, V: - between conductors and cable screen - between conductors of operating pairs of cable |
DC |
750 1000 |
Type of EFA |
EFA value for cables |
Operating temperature, °С | -40 to +50 |
Installation temperature, °С | -10 to +50 |
Storage and transportation temperature, °С | -40 to +50 |
Minimum installation temperature, °С | -10 |
Relative humidity at +35 °С,% | 98 |
J |
-Y |
(St) |
Y | 2 | х2 | х0,8 | +0,6 |
|
||||
Diameter of tinned copper conductor |
||||||||||||
Diameter of insulated conductor |
||||||||||||
Paired core |
||||||||||||
Number of pairs in the core |
||||||||||||
Outer sheath of PVC compound |
||||||||||||
Cable with electrostatic screen |
||||||||||||
Conductor insulation of PVC compound |
||||||||||||
Cable type |