Cable terminations rek-10HH2-3-М, rek-10HH2-3-А-М for outdoor installation and rek-10HH-3-М, rek-10HH-3-А-М for internal installation

For 3-core cables with insulation of vulcanized (cross-linked) polyethylene for a voltage of 6 and 10 kV.

Technical performance

rek-10HH2-3-М, rek-10HH2-3-А-М and rek-10HH3-М, rek-10HH-3-А-М – terminations using tracking-resistant heat-shrinkable tubing.

Termination set includes:

  1. Universal lugs with breakaway head manufactured by GPH;
  2. Special tapes;
  3. Tracking-resistant heat-shrinkable tubes;
  4. Heat-shrinkable cable sleeve joint;
  5. Tracking-resistant heat-shrinkable insulators;
  6. Kit for connecting the shield and armor;
  7. Installation instructions.

Termination design

Core termination is carried out with the use of lugs with breakaway head. The cable sheath end is sealed with a heat-shrinkable sleeve joint.

As the main electrical insulating material, a heat-resistant heat-shrinkable tube is placed on each conductor and an appropriate number of heat-shrinkable insulators that are resistant to environmental influences and leakage currents is installed. The joint use of HST with the adhesive layer and special tapes ensures complete sealing of the cable termination. The grounding of the cable shield is made without soldering.

In the rek-10HH2-3-А-М and rek-10HH-3-А-М terminations, the armor of the cable is earthed without soldering using a special armor outlet kit.

Installation

  • cable preparation is carried out in accordance with the installation instructions for the termination;
  • To remove the semiconducting layer from the core insulation, using special tools is recommended.

Supply

At the customer’s request, the sets can be supplied without sleeves or with sleeves for crimping for copper or aluminum conductors. The length of the conductor termination length by agreement with the customer can be increased to 1200 mm.

Application

rek-10HH2-3-М and rek-10HH-3-М – terminations are designed for outdoor and indoor termination of 3-core cables with cross-linked polyethylene insulation, with a PVC sheath (rek-10HH2-3-А-М and rek-10HH-3-А-М for cables armored with steel tapes or wires*), for voltage of 6 and 10 kV operated at ambient temperature from -50 C to +50 C, with relative humidity up to 80%.

Characteristics

Cable terminations rek-10HH-3-М and rek-10HH-3-А-М correspond to ST TOO 143-1930-10-16-29-2012 and meet the requirements of GOST 13781.0-86.

Cable type

For 3-core cables of the following makes: (manufactured in Russia) APvEp-6/10, APvEgP-6/10, APvEgaP6 / 6/10, PvEP-6/10, PvEgaP-6/10, PvEgP-6/10, etc.; (imported production, standard TS, VDE) N2XS2Y, N2XS2Y, NA2XS2Y, NA2XSY, N2XSEY, 2XSEY, A2XSEY etc.

TABLE FOR ORDERING TERMINATIONS FOR INDOOR INSTALLATION

Rated voltage (kV) Conductor cross-section (mm²) Number of conductors in cable Ordering designation Termination length, (mm), (L min)
unarmored cables cables with tape armor
6 and 10 35/50
3
rek-10HH-3-35/50-M rek-10HH-3-35/50-А-M 500
6 and 10 50/120
3
rek-10HH-3-50/120-M rek-10HH-3-50/120-А-M 500
6 and 10 120/240
3
rek-10HH-3-120/240-M rek-10HH-3-120/240-А-M 500
6 and 10 300
3
rek-10HH-3-300-M rek-10HH-3-300-А-M 500

TABLE FOR ORDERING TERMINATIONS FOR OUTDOOR INSTALLATION

Rated voltage (kV) Conductor cross-section (mm²) Number of conductors in cable Ordering designation Termination length, (mm), (L min)
unarmored cables cables with tape armor
6 and 10 35/50
3
rek-10HH2-3-35/50-M rek-10HH2-3-35/50-А-M 1000
6 and 10 50/120
3
rek-10HH2-3-50/120-M rek-10HH2-3-50/120-А-M3 1000
6 and 10 120/24
3
rek-10HH2-3-120/240-M rek-10HH2-3-120/240-А-M 1000
6 and 10 300
3
rek-10HH2-3-300-M rek-10HH2-3-300-А-M 1000

* Termination sets for cable with wire armor shall be ordered separately.