RUS

Cable terminations rek-10KnTK-SL-M for outdoor installation and rek-10KvTK-SL-M for indoor installation

Cable terminations rek-10KnTK-SL-M for outdoor installation and rek-10KvTK-SL-M for indoor installation for 3-core cables with impregnated paper insulation for 6 and 10 kV voltage.

Technical performance

Heat-shrinkable terminations with the use of polyurethane compound are used for cables with aluminum or lead sheath, with impregnated paper insulation, for 6 and 10 kV voltage.


Termination set includes:

  1. Universal lugs with breakaway head manufactured by GPH;
  2. Special tapes;
  3. Heat-shrinkable tubing and insulators;
  4. Polyurethane compound;
  5. Bonding kit using a solderless system, which includes a ground wire and spring rings;
  6. Polyethylene heat-shrinkable case;
  7. Installation instructions.

Termination design

Cable conductors with impregnated paper insulation are coated with an 800 mm oil-resistant heat-shrinkable insulation tube.
Alignment of the electric field on the cable sheath end is made with a special tape having a high dielectric constant, and the sheath end is sealed with a polyethylene heat-shrinkable case and polyurethane compound.

The insulating conductors are fitted with the appropriate number of heat-shrinkable insulators resistant to the environment and leakage current. The space between the lugs and the insulation of the conductors is sealed with mastic and heat-shrinkable tube with an adhesive layer. The ground wire with the tip is attached to the metal sheath and armor using spring rings.

Installation

  • the sealing-in of the termination edge can be performed both in the vertical and horizontal position of the cable.

Technological features

  • processing of the space between the conductors in the cable sheath end is not required;
  • test voltage is supplied immediately after installation;
  • admissible height difference along the cable length is 25 meters;
  • no special tools required.

Testing

Cable terminations rek-10KnTK-SL-M and rek-10KvTK-SL-M are tested in accordance with GOST 13781.0-86.

Characteristics

Cable terminations rek-10KnTK-SL-M and rek-10KvTK-SL-M correspond to ST TOO 143-1930-10-16-29-2012 and meet the requirements of GOST 13781.0-86.

Supply

At the customer’s request, the sets can be supplied without lugs or with lugs for crimping for copper or aluminum conductors.
Standard conductor termination length is 800 mm. The length of the conductor termination length (L2) by agreement with the customer can be increased to 1200 mm.
Example for ordering a termination with an increased conductor termination length: rek-10KnTK-3-35/50-SL/1200-М.

Cable type

AABG, ASBG, SBG, AABlU, ASBlU, SBN, AASHvU, AASHp, AAB2lSHvU, ASB2lSHvU, SB2lSHv, SBlU etc.

TABLE FOR ORDERING REK-10KNTK-SL-M TERMINATIONS

Rated voltage, kV Conductor cross-section, mm2 Designation for ordering terminations for outdoor installation Designation for ordering terminations for indoor installation Dimensions, mm
Length, (L1 max) Length, (L2 max)
6 and 10 16/25 rek-10КнТК-3-16/25-СЛ-М rek-10КвТК-3-16/25-СЛ-М 1000
800
6 and 10 35/50
rek-10КнТК-3-35/50-СЛ-М rek-10КвТК-3-35/50-СЛ-М 1020
800
6 and 10 70/120
rek-10КнТК-3-70/120-СЛ-М rek-10КвТК-3-70/120-СЛ-М 1040
800
6 and 10 150/240
rek-10КнТК-3-150/240-СЛ-М rek-10КвТК-3-150/240-СЛ-М 1060
800