Cable terminations rek-10KnT-SL-M for outdoor installation and rek-10KvT-SL-M for indoor installation

For 3-core cables with impregnated paper insulation, for voltage of 6 and 10 kV.

Technical performance

Rek-10KnT-SL-M and rek-10KvT-SL-M heat-shrinkable terminations are used for cables with aluminum or lead sheath, with impregnated paper insulation, for 6 and 10 kV voltage. Termination set includes:

  1. Universal lugs with breakaway head manufactured by GPH;
  2. Special tapes;
  3. Heat-shrinkable tubing and insulators;
  4. Bonding kit using a solderless system, which includes a ground wire and spring rings;
  5. Heat-shrinkable cable sleeve joint;
  6. Installation instructions.

Termination design

Cable conductors with impregnated paper insulation are coated with an oil-resistant heat-shrinkable insulation tube. The equalization of the electric field intensity in the cable sheath end is made with the use of special mastic with high dielectric constant. The cable sheath end is sealed with a heat-shrinkable cable sleeve joint. The insulated conductors are fitted with tracking-resistant heat-shrinkable tubes and the appropriate number of heat-shrinkable insulators resistant to the environment and leakage current. The space between the lugs and the insulation of the conductors is sealed with mastic and heat-shrinkable tube with an adhesive layer.

Testing

Cable terminations rek-10KnT-SL-M and rek-10KvT-SL-M are tested in accordance with GOST 13781.0-86.

Note

The length of the conductors can be determined at the installation site.
The minimum conductor length is 450 mm.

Cable type

AABG, ASBG, SBG, AABlU, ASBlU, SBN, AASHvU, AASHp, AAB2lSHvU, ASB2lSHvU, SB2lSHv, SBlU etc.

Characteristics

Cable terminations rek-10KnT-SL-M and rek-10KvT-SL-M correspond to ST TOO 143-1930-10-16-29-2012 and meet the requirements of GOST 13781.0-86.

Supply

At the customer’s request, the sets can be supplied without lugs or with lugs for crimping for copper or aluminum conductors.
Standard conductor termination length is 800 mm.

TABLE FOR ORDERING REK-10KNT-SL-M TERMINATIONS

Rated voltage, kV Conductor cross-section, mm2 Designation for ordering terminations for outdoor installation Designation for ordering terminations for indoor installation Dimensions, mm
Length, (L1 max) Length, (L2 max)
6 and 10 16/25 rek-10КнТ-3-16/25-СЛ-М rek-10КвТ-3-16/25-СЛ-М 1000
800
6 and 10 35/50
rek-10КнТ-3-35/50-СЛ-М rek-10КвТ-3-35/50-СЛ-М 1020
800
6 and 10 70/120
rek-10КнТ-3-70/120-СЛ-М rek-10КвТ-3-70/120-СЛ-М 1040
800
6 and 10 150/240
rek-10КнТ-3-150/240-СЛ-М rek-10КвТ-3-150/240-СЛ-М 1060
800