Cable terminations 10KnTp-SL-nb for outdoor installation and 10KvTp-SL-nb for indoor installation

10KnTp-SL-nb and 10KvTp-SL-nb heat-shrinkable terminations are used for cables with aluminum or lead sheath, with impregnated paper insulation, for 6 and 10 kV voltage.
HEAT-SHRINKABLE TERMINATION INSTALLATION TECHNOLOGY

Termination set includes:

  1. Universal lugs with breakaway head;
  2. Special tapes and mastic;
  3. Heat-shrinkable tubing and insulators;
  4. Heat-shrinkable cable sleeve joint;
  5. Cable bonding kit using a combined system, which includes a ground wire, soldering kit and spring rings;
  6. Installation instructions.

Termination design

The insulated conductors are fitted with tracking-resistant heat-shrinkable tubes. The equalization of the electric field intensity in the cable sheath end is made with the use of special mastic with high dielectric constant. The ground wire is fixed on the cable sheath and armor using a spring ring and soldering. The cable sheath end is sealed with a heat-shrinkable tube and a cable sleeve joint.

The outdoor use terminations are fitted with the appropriate number of heat-shrinkable insulators resistant to the environment and leakage current. The space between the lugs and the insulation of the conductors is sealed with mastic and heat-shrinkable tube with an adhesive layer.

Testing

10KnTp-SL-nb and 10KvTp-SL-nb terminations are tested in accordance with GOST 13781.0-86.

Note

The length of the conductors can be determined at the installation site. The minimum conductor length is 450 mm.

Cable type

AABG, ASBG, SBG, AABlU, ASBlU, SBN, AASHvU, AASHp, AAB2lSHvU, ASB2lSHvU, SB2lSHv, SBlU etc.

Characteristics

10KnTp-SL-nb and 10KvTp-SL-nb terminations meet the requirements of GOST 13781.0-86.

Supply

At the request of the customer, kits without lugs can also be delivered. Standard conductor termination length is 800 mm.

ORDERING TABLE

Rated voltage (kV) Conductor cross-section (mm2) Designation for ordering terminations for outdoor installation Designation for ordering terminations for indoor installation Dimensions (mm)
Length (L1 max) Length (L2 max)
6 and 10
16/25
10КнТп-3-16/25-СЛ-нб 10КвТп-3-16/25-СЛ-нб 1030
800
6 and 10 35/50
10КнТп-3-35/50-СЛ-нб 10КвТп-3-35/50-СЛ-нб 1030
800
6 and 10 70/120
10КнТп-3-70/120-СЛ-нб 10КвТп-3-70/120-СЛ-нб 1030
800
6 and 10 150/240
10КнТп-3-150/240-СЛ-нб 10КвТп-3-150/240-СЛ-нб 1030
800

Order